Technical Parameters | Technical Indicators |
Protector auxiliary power supply | AC/DC110/220V or AC380V, power comsumption 15VA |
Rated working voltage of the motor | AC380V / 660V, 50Hz / 60Hz |
Rated operating current of the motor | 1 (0.1A-5000A) | Adopt measurement module |
5 (0.1A-5000A) |
25(6.3A-25A) |
100(25A-100A) |
250(63A-250A) | Adopt outlay current tansformer and measurement module |
800(250A-800A) |
Leakage | 50mA-1A or 3A-30A | Adopt measurement module and leakage current transformer |
Relay output contact capacity | Impedance load | AC250V、6A; DC24V、6A |
Master switching input and output | 4DI/4DO |
Switching value module | 4DI/3DO |
Temperature module | Type of external sensor: PT100、PT1000、Cu50、PTC、NTC Channel of the sensor: 3 channels Sensor’s corresponding measurement range: PT100/PT1000: -50°C~+500°C; Cu50: -50°C~+150°C; PTC/NTC: 100Ω~30kΩ |
Analog module | 2-channel 4-20mA input and 2-channel 4-20mA output |
Master communiction | RS485 Modbus_RTU |
Communication module | Double RS485 Modbus_RTU, Profibus_DP |
Environment | Working temperature | -10ºC~55ºC |
Storage temperature | -25ºC~70ºC |
Relative humidity | ≤95﹪No condensation, no corrosive gas |
Altitude | ≤2000m |
Pollution levels | Class 3 |
Protection grade | Main body IP20, split display module IP45 (installed on the cabinet panel) |
Installation category | Level III |