Input | DC rated voltage | 1 channel: 0-48VDC |
DC current | 6 channels hall sensors: total 200A/5V, China Telecom, China Mobile, China Unicom and the 1st channel reserve 50A/5V, 2nd channel reserve 100A/5V |
Commercial power monitoring | 1 channel: 0-5VDC |
Overload capacity | Voltage: 1.2 times continued, 2 times continued 1s; Current: 1.2 times continued, 10 times continued 1s |
Accuracy (superposition hall sensors)
| 1%ln≤ l ≤10% ln error±2.5%; l>10%ln error±2% |
Measurement resolution | Voltage: 0.01V, Current: 0.01A, Power: 0.01kw, Energy: 0.01kwh |
Functions | Basic function | Monitor device system time, total voltage, total current, power energy, each channel voltage, current, power, energy; LED display, RS485 communication |
Metering function | Start current: under rated voltage, when the load current value of the meter doesn't exceed 1% of the max current,the meter start. Shunt running current: when there is no current in the current circuit of the meter, and 85%-125% of the rated voltage is applied on the voltage circuit, the calculator shall not have more than one digital change. |
Alarm function | DC under-voltage, DC over-voltage, one power down, module voltage loss, metering branch error, internal program error, clock error, memory failure, AC input power failure.
|